Energy-saving Control Strategy for Data Center Cooling System Based on Internet of Things (IoT) Perception
Xinyi Sun
NYU Tandon School of Engineering, New York University, Brooklyn, NY 11201, USA.
*Corresponding author: Xinyi Sun
Published: September 24, 2026
Abstract
The rapid migration of IT loads, the difference in
the heat density of the rack, and the coupling operation of equipment are easy
to cause local overheating of the data centre and excessive cooling in other
areas. Focussing on this supply and demand deviation, we build an energy-saving
control strategy based on the perception of the Internet of Things (IoT), and
use the rack inlet and outlet temperature, IT power, channel pressure
difference, return air parameters, chilled water temperature difference, flow,
and equipment power as input. The edge node is responsible for time synchronisation,
abnormal data repair, and thermal state reconstruction, and the prediction
module estimates the short-term cold load and hot spot migration trend. The
control layer adopts a double closed-loop structure that combines equipment
rapid response and system rolling optimisation to dynamically adjust the air
supply temperature, fan speed, pump frequency, valve opening, and water chiller
unit load rate, and embeds the upper temperature limit, minimum flow rate,
start-stop interval, actuator change rate, and communication fault constraints.
The virtual cold station with public operation data and actual measurement data
calibration is used to compare the differences between fixed setting values,
PID, and perception-driven control in refrigeration energy consumption, thermal
safety, control fluctuations, and prediction errors.
Keyword
Internet of Things (IoT); data center cooling; energy-saving control; thermal state estimation; model predictive control
References
[1] Zhang Q, Meng Z, Hong X, et al. A survey on data center cooling systems: technology, power consumption modeling and control strategy optimization. J Syst Archit. 2021;119:102253.
[2] Wang J, Tong X, Yue C, et al. Real-time temperature distribution reconstruction via linear parameter-varying state-space model and Kalman filter in rack-based cooling data centers. Build Environ. 2023;242:110601.
[3] Mirhoseininejad S, Badawy G, Down DG, et al. A data-driven, multi-setpoint model predictive thermal control system for data centers. J Netw Syst Manage. 2021;29:7.
[4] Mahbod MHB, Chng CB, Lee PS, et al. Energy saving evaluation of an energy efficient data center using a model-free reinforce-ment learning approach. Appl Energy. 2022;322:119392.
[5] Deng W, Wang J, Yue C, et al. Model-based control strategy with linear parameter-varying state-space model for rack-based cooling data centers. Energy Build. 2024;319:114528.
[6] Lu R, Li X, Chen R, et al. An alternative reinforcement learning (ARL) control strategy for data center air-cooled HVAC systems. Energy. 2024;308:132977.
[7] Lin J, Lin W, Lin W, et al. Multi-objective cooling control optimization for air-liquid cooled data centers using TCN-BiGRU-Attention-based thermal prediction models. Build Simul. 2024;17(12):2145-2161.
[8] Wu S, Zheng W, Wang Z, et al. AlphaDataCenterCooling: a virtual testbed for evaluating operational strategies in data center cooling plants. Appl Energy. 2025;380:125100.
[9] Kahil H, Sharma S, Välisuo P, et al. Reinforcement learning for data center energy efficiency optimization: a systematic literature review and research roadmap. Appl Energy. 2025;389:125734.
Copyright
© 2026 by the author(s).
This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution-NonCommercial-NoDerivatives (CC BY-NC-ND) license, which permits non-commercial use, distribution, and reproduction in any medium, provided the original work is properly cited and is not modified or adapted.
https://creativecommons.org/licenses/by-nc-nd/4.0/
How to cite this paper
Energy-saving Control Strategy for Data Center Cooling System Based on Internet of Things (IoT) Perception
How to cite this paper: Xinyi Sun. (2026) Energy-saving Control Strategy for Data Center Cooling System Based on Internet of Things (IoT) Perception. Advances in Computer and Communication, 7(3), 196-200.
DOI: http://dx.doi.org/10.26855/acc.2026.09.017